92 Calibrating Using the Auto Calibration Method EAGLE 2 Operator’s Manual
12. Press and release the POWER ENTER RESET button. The following
screen appears.
13. If you select YES by pressing and releasing the AIR YES button, the
changes that you made will be saved in the EAGLE 2’s memory as the
new auto calibration gas values.
If you select NO by pressing and releasing the DISPLAY ADJUST NO
button, the changes you made will be used for any calibrations performed
during the current operating session only. The EAGLE 2 will delete the
changes when the unit is turned off and will load the previous set of auto
calibration values when it is turned on again.
14. When you make your selection and press the desired button, the unit
returns to the Calibration Gas Values Screen.
15. Press and release the POWER ENTER RESET button to proceed to the
Calibration In Process Screen. CAL IN PROCESS is flashing.
If you do not want to proceed with the calibration, press and release the
DISPLAY ADJUST NO button to return to the Calibration Gas Values
Screen.
If you do want to continue with the calibration, proceed to the next step.
16. Connect the gas bag tubing to the regulators or dispensing valve’s hose
barb fitting.
DO YOU WANT TO
STORE NEW VALUE(S)
IN MEMORY FOR
FUTURE CALIBRATIONS?
PRESS YES OR NO
CAL GAS VALUES
CH4 50 %LEL
OXY 12.0 vol%
H2S 25.0 ppm
CO 50 ppm
ENTER TO BEGIN CAL
CAL IN PROCESS
CH4 0 %LEL
OXY 20.9 vol%
H2S 0.0 ppm
CO 0 ppm
ENTER WHEN DONE