10 FIREYE
®
System Components
Phoenix Scanners 85UVF and IRF
The Fireye Phoenix type 85UVF/IRF flame scanners
are microprocessor based devices utilizing a solid state
flame detection sensor. The Phoenix flame scanners incor-
porate an internal flame relay with automatically set ON/
OFF thresholds, thereby eliminating the need for a remote
flame amplifier or flame switch.
Phoenix scanners detect the amplitude of the modula-
tions (the flame “flicker”) that occur within the targeted
flame, over a wide frequency. During the scanner setup
procedure, the amplitudes of the target flame are automati-
cally stored by the flame scanner, together with optimum
ON/OFF criteria. The appropriate sensor gain is automati-
cally selected. Phoenix scanners incorporate full self diag-
nostics and electronic self checking.
The Phoenix 85UVF/IRF is available in multiple models differentiated by detection cell type, levels of
hazardous area certifications and agency approvals.
The Phoenix 85UVF/IRF flame scanner is powered by 24Vdc. Electrical connection is via an 8-pin electri-
cal quick-disconnect (QD). An analog 4 to 20mA output of flame strength is standard.
Operator interface to the Phoenix scanner is via a pushbutton keypad and informative LEDs. These provide
continuous indication of flame signal, flame relay status, scanner status as well as selected mode of opera-
tion. Simplified keystroke routines are used for setup and this can be completed in seconds. For remote
interface, outputs are provided for flame switch, fault relay and 4 to 20mA flame strength.
Note: The Phoenix QD models with electrical quick-disconnect have replaced the original models
equipped with ten feet of captive cable. The QD models (with 59-546-x cables) are suitable for use in Class
I Division 2 hazardous areas, thereby eliminating the need for "EX" models. The "CEX" models remain
unchanged for use in EEx d IIC T6 hazardous areas.
Refer to bulletins CU-114 and CU-115.
TYPE/MODEL
FREQ.
HZ.
WAVELENGTH
(nanometers)
MOUNTING
FLANGE
AMBIENT
TEMP. MAX.,
MIN.
SAFETY
APPROVALS
NOTES
85IRF1-1QD
700-1700 1” NPT
UL C/US, FM,
DIN, CE
85IRF4-1QDWR
24 VDC
(P/N 35-318-1)
or
150 (65 C)
-40 F (-40 C)
UL C/US, FM
See page 5 for complete
model listing.
85UVF1-1QD
295-320 1” BSP
UL C/US, FM,
DIN, CE
85UVF4-1QDWR (P/N 35-318-2)
ordered
separately
UL C/US, FM